INSTALLATION OF STI-1221E STROBE DAMAGE STOPPER
®
All specifications and information shown were current as of publication and are subject to change without notice.
INSTALLATION NOTES
1. To minimize strobe light loss, regardless of the type of strobe appliance used, center cover over
the strobe light lens. Failure to follow these instructions may lead to light loss transmission.
2. Damage Stopper must be installed to comply with applicable NEC, NFPA and local codes.
3. In applications where wash downs, rainfall or condensation occur, it is recommended that a
drain or weep hole be provided. Refer to weep hole installation diagram.
4. Damage Stopper may be installed outdoors when appliance carries an outdoor rating.
Electronic warranty form at www.sti-usa.com/wc14
1221EIS APRIL2006
CLEANING INSTRUCTIONS
Rinse with water to remove abrasive dust and dirt. Wash with soap or mild
detergent, using a soft cloth (do not scrub). Rinse once more then dry with a
soft cloth or chamois. To remove grease or wet paint, rub gently with a cloth
wetted with naphtha. Then wash and rinse. DO NOT USE RAZOR BLADES.
INSTALLATION INSTRUCTIONS - REFER TO EXPLODED VIEW
1. Using back box assembly as a template, place against mounting surface
at proper location according to NFPA 72.
2. Mark and drill (4) holes 1/4 in. (6.3mm) diameter, 1 in. (25mm) deep.
4. Insert the (4) anchors into the wall.
4. Mount frame assembly to wall with screws.
5. Install electrical fittings as needed.
6. Install strobe appliance (except for retrofit applications).
7. Install cover with clips and screws.
8. Test appliance according to appliance manufacturer’s instructions.
INTERNAL DIMENSIONS
WEEP HOLE INSTALLATION
INSTALL CLAMP IN NOTCH 2 AS SHOWN
629764 CLAMP
(4) PROVIDED
19013 SCREW
#10 x 1 1/2 in.
(4) PROVIDED
19033 ANCHOR
(4) PROVIDED
LOCATED IN THIS AREA
DRILL A .25 in.(6.3mm) DIA. HOLE
APPROX
CENTER LINE
OF UNDERSIDE OF
COVER
1 in.(25mm)
1
2
EXISTING FLUSH MOUNT
STROBE APPLIANCE
06297E FRAME ASSY.
DEPTH
4 in.(102mm)
WIDTH
6.5 in.(165mm)
IF ADDED PROTECTION IS
NEEDED DUE TO ENVIROMENTAL
CONDITIONS ORDER SUB-121
ENVIRO KIT
01221 COVER ONLY
!
01221 COUVERCLE SEULEMENT
HEIGHT
8.5 in.(216mm)
19047 #8-32 x 3/8 in.
SOCKET HEAD CAP SCREW
(4) PROVIDED
629764 CLAMP
(4) PROVIDED
19013 SCREW
#10 x 1 1/2 in.
(4) PROVIDED
19033 ANCHOR
(4) PROVIDED
LOCATED IN THIS AREA
DRILL A .25 in.(6.3mm) DIA. HOLE
APPROX
CENTER LINE
OF UNDERSIDE OF
COVER
1 in.(25mm)
1
2
EXISTING FLUSH MOUNT
STROBE APPLIANCE
06297E FRAME ASSY.
DEPTH
4 in.(102mm)
WIDTH
6.5 in.(165mm)
IF ADDED PROTECTION IS
NEEDED DUE TO ENVIROMENTAL
CONDITIONS ORDER SUB-121
ENVIRO KIT
01221 COVER ONLY
!
01221 COUVERCLE SEULEMENT
HEIGHT
8.5 in.(216mm)
19047 #8-32 x 3/8 in.
SOCKET HEAD CAP SCREW
(4) PROVIDED
REMARQUES SUR L’INSTALLATION
1. Afin de minimiser la perte de lumière stroboscopique, quel que soit le type de stroboscope
utilisé, le couvercle doit être centré sur l’objectif stroboscopique. Le fait d’omettre ces
instructions risque d’entraîner la perte de diffusion de la lumière.
2. Le Stopper de dégâts doit être installé de sorte à être conforme avec les normes NEC, NFPA
applicables et les codes locaux.
3. Dans les applications où des jets d’eau, des précipitations ou de la condensation se produisent,
il est recommandé de prévoir un trou de vidange ou une barbacane. Reportez-vous à schéma
d’installation d’une barbacane.
4. Il est possible d’installer un Stopper de dégâts à l’extérieur lorsque l’appareil est homologué
pour utilisation à l’extérieur.
Page view 0
1 2

Summary of Contents

Page 1 - REMARQUES SUR L’INSTALLATION

Safety Technology International, Inc.2306 Airport Road • Waterford, Michigan 48327-1209Phone: 248-673-9898 • Fax: 248-673-1246Toll Free: 800-888-4784

Page 2 - STI-1210 / STI-1221 SERIES

• This enclosure is rated to protect signaling appliances indoors and in areas of indirect weather exposure.The cover may be used outdoors only with d

Comments to this Manuals

No comments